Complete wiring, VFD parameters, RichAuto handle setup and troubleshooting for an HQD spindle in 3-line 8-status (multi-step speed) mode. Follow it in order to avoid the most common commissioning trap on this combination.
This guide commissions a DV203 VFD driving an HQD spindle through a RichAuto A11 DSP handle in 3-line 8-status mode — 1 forward line plus 3 binary speed bits, giving 8 speed steps the operator can change from the handle without touching the VFD. It is the production standard for CNC routers.
The DV203 ships with factory defaults on inputs X2, X3, X4 that conflict with RichAuto multi-step wiring. Following this guide as written avoids the classic trap: the spindle running on alternate gears, paired speeds, or random direction changes.
| Item | Specification |
|---|---|
| VFD | DV203 series, sized to spindle power (e.g. DV203-2R2G for 2.2 kW HQD) |
| Controller | RichAuto DSP A11 handle + interface board + 50-pin cable |
| Spindle | HQD GDZ-series, 2-pole, 400 Hz rated. Spindle voltage MUST match VFD output. |
| Control cable | 5-core shielded, 0.5–1.0 mm² per core, RichAuto J7 → DV203 inputs |
| Spindle power cable | 4-core shielded (U/V/W + earth), 1.5–2.5 mm² by power |
| Brake resistor (optional) | For high-inertia / fast-decel jobs — size per DV203 manual |
RichAuto outputs are NPN open-collector (active-low) — they sink to ground when active. The DV203 default with the +24V/OP shorting tab in factory position is exactly what's needed.
| Wire (typical colour) | RichAuto pin | Function | DV203 terminal |
|---|---|---|---|
| Red | Y1 | Spindle FWD ON/OFF | X1 |
| Green | Y2 | Speed bit 0 (LSB) | X2 |
| Black | Y3 | Speed bit 1 | X3 |
| Yellow | Y4 | Speed bit 2 (MSB) | X4 |
| Blue | GND | Common ground | COM |
Wire colours vary by cable batch — always confirm by terminal name, not colour.
| Parameter | Default | Default function (wrong) | Required setting |
|---|---|---|---|
P4-00 (X1) | 1 | FWD (Forward run) | 1 — keep ✓ |
P4-01 (X2) | 4 | FJOG — wrong! | 12 — Multi-segment terminal 1 |
P4-02 (X3) | 9 | Fault Reset — wrong! | 13 — Multi-segment terminal 2 |
P4-03 (X4) | 12 | Multi-seg 1 — wrong slot! | 14 — Multi-segment terminal 3 |
P4-04 (X5) | 13 | Multi-seg 2 | 0 — disabled |
Confirming this is the cause: spindle runs on every alternate gear (S1 stops, S2 runs…), or speeds appear in pairs, and the VFD throws no error. Fix in 60 s: P4-01=12, P4-02=13, P4-03=14, P4-04=0, save, retest.
Keypad: ESC/PRG to enter, ▲/▼ to navigate, SET to edit, SHIFT/>> to move digits, SET to save & advance, ESC to exit.
| Parameter | Set to | Description |
|---|---|---|
P0-01 | 2 | V/F control (correct for HQD async spindle) |
P0-02 | 1 | Run command from terminal (RichAuto Y1 controls FWD) |
P0-03 | 6 | Frequency source = Multi-segment |
P0-10 | 400.00 | Max frequency for 24,000 RPM (use 300 if 18,000 RPM spindle) |
P0-12 | 400.00 | Upper limit frequency |
P0-14 | 0.00 | Lower limit (allows 0 RPM stop) |
P0-17 | 10.0 | Accel time (s). Raise to 12–15 if Er02 on accel |
P0-18 | 10.0 | Decel time (s). Raise to 12–15 if overvoltage on decel |
| Parameter | Set to | Notes |
|---|---|---|
P1-00 | 0 | Standard async motor |
P1-01 | Nameplate kW | e.g. 1.5 / 2.2 / 3.0 / 4.5 |
P1-02 | Nameplate V | 220 V or 380 V — must match VFD output & spindle |
P1-03 | Nameplate A | Rated current. Too low → nuisance trips |
P1-04 | 400.00 | Rated frequency (300 if 18,000 RPM) |
P1-05 | 24000 | Rated RPM (2-pole at 400 Hz) |
P1-37 | 2 (then RUN) | Auto-tuning trigger — Section 6 (no tool in collet) |
| Parameter | Set to | Notes |
|---|---|---|
P3-00 | 0 | Linear V/F — correct for high-speed spindle |
P3-01 | 0.0–2.0 | Torque boost. 0.0 (auto) fine for most spindles |
| Parameter | Set to | Function |
|---|---|---|
P4-00 (X1) | 1 | FWD (Forward run) |
P4-01 (X2) | 12 | Multi-seg terminal 1 — MUST change from default 4 |
P4-02 (X3) | 13 | Multi-seg terminal 2 — MUST change from default 9 |
P4-03 (X4) | 14 | Multi-seg terminal 3 — MUST change from default 12 |
P4-04 (X5) | 0 | No function (unused) |
P4-11 | 0 | Two-line type 1 |
Each PC value is a % of max frequency P0-10. These must match the RichAuto handle speeds (Section 7).
| Gear | PC param | % | Hz | RPM |
|---|---|---|---|---|
| S1 | PC-00 | 0.0 | 0 | 0 — Stop |
| S2 | PC-01 | 25.0 | 100 | 6,000 |
| S3 | PC-02 | 37.5 | 150 | 9,000 |
| S4 | PC-03 | 50.0 | 200 | 12,000 |
| S5 | PC-04 | 62.5 | 250 | 15,000 |
| S6 | PC-05 | 75.0 | 300 | 18,000 |
| S7 | PC-06 | 87.5 | 350 | 21,000 |
| S8 | PC-07 | 100.0 | 400 | 24,000 (max) |
Auto-tuning measures the spindle's real electrical parameters and writes them to the VFD. Skipping it gives weak low-RPM torque and rough running.
P1-37, set = 2 (full dynamic; use 1 static if it can't spin freely).Both under Menu → Machine Setup → Spindle Setup. Password if asked: 123 or 459.
| Gear | Hz | RPM | Typical use |
|---|---|---|---|
| S1 | 0 | 0 | Stop / minimum |
| S2 | 100 | 6,000 | Engraving, soft material |
| S3 | 150 | 9,000 | Plywood, plastic, soft wood |
| S4 | 200 | 12,000 | MDF, hardwood, acrylic |
| S5 | 250 | 15,000 | 3D carving, fine detail |
| S6 | 300 | 18,000 | Aluminium, brass (light cuts) |
| S7 | 350 | 21,000 | V-bit, detailed engraving |
| S8 | 400 | 24,000 | Max — finishing only |
| Cause | Action |
|---|---|
| Y1 not reaching X1 | Check interface LED on spindle command; meter X1 to COM |
| Command source not terminal | Verify P0-02 = 1 |
| All handle speeds = 0 | Check Spindle Setup gear values |
| VFD fault (Er.XX) | Read code, see 9.5 |
| +24V/OP tab removed | Power off, replace tab |
Cause: P4-01 still at default 4 (FJOG). Fix: P4-01 = 12. Save, retest.
Cause: a speed-bit input is dead, usually bit 0 (Y2/X2).
Cause: PC values don't match handle speeds. Fix: re-enter 5.5 to match 7.3.
| Code | Meaning | Action |
|---|---|---|
Er02 | Accel overcurrent | Raise P0-17 to 15 s; check tool jam; verify P1-03 |
Er03 | Decel overcurrent | Raise P0-18 to 15 s; add brake resistor |
Er04 | Const-speed overcurrent | Reduce load, sharpen tool, verify sizing |
Er05/06/07 | Overvoltage | Increase decel; add brake resistor; check supply |
Er09 | Undervoltage | Check mains; add stabiliser |
Er10 | VFD overload | Undersized; check carrier frequency |
Er11 | Motor overload | Bearings seizing / load high; check P1-03 |
Er14 | Module overheat | Fan dead / dust / hot ambient |
Er19 | Auto-tune failure | Bad motor wiring; check U/V/W & P1-01…05 |
Er23 | Output short to ground | Insulation failed — megger test |
| RichAuto | Wire | DV203 |
|---|---|---|
Y1 | Red | X1 (FWD) |
Y2 | Green | X2 (Multi-seg 1) |
Y3 | Black | X3 (Multi-seg 2) |
Y4 | Yellow | X4 (Multi-seg 3) |
GND | Blue | COM |
P0-01=2 · P0-02=1 · P0-03=6 · P0-10=400
P0-17=10 · P0-18=10
P1-00=0 · P1-01..05=nameplate · P1-37=2 (then RUN)
P3-00=0 · P3-01=0.0–2.0
P4-00=1 · P4-01=12 · P4-02=13 · P4-03=14 · P4-04=0 · P4-11=0
PC-00=0 · PC-01=25 · PC-02=37.5 · PC-03=50
PC-04=62.5 · PC-05=75 · PC-06=87.5 · PC-07=100