NK105 + Kinco CV100
Water-cooled spindle


1. Overview
The Kinco CV100 is a reliable VFD for larger water-cooled HQD spindles (3.0–5.5 kW). With a Weihong NK105 controller, the spindle runs in multi-step terminal mode: the NK105 sets speed via binary-coded relay outputs into the CV100's multi-reference inputs, so the operator selects gears S1–S8 from the handle. The water-cooled spindle adds one hard requirement: coolant must flow before and during every run.
2. Required Hardware
| Item | Specification |
|---|---|
| VFD | Kinco CV100, sized to spindle (e.g. CV100-4T5R5G for 5.5 kW, 380 V) |
| Controller | Weihong NK105 (G2/G3) + terminal board |
| Spindle | HQD water-cooled, 2-pole, 400 Hz, 380 V (verify nameplate) |
| Coolant system | Pump + radiator/tank, flow switch recommended |
| Control cable | Shielded multi-core 0.5–1.0 mm² |
| Power cable | 4-core shielded (U/V/W + earth) 2.5–4.0 mm² for 5.5 kW |
3. Wiring — Control (NK105 board → CV100 inputs)
| Wire (typical colour) | NK105 output | Function | CV100 terminal |
|---|---|---|---|
| Red | SPIN-FWD | Run forward ON/OFF | DI1 (FWD) |
| Green | S1 / bit0 | Multi-reference bit 0 | DI3 |
| Black | S2 / bit1 | Multi-reference bit 1 | DI4 |
| Yellow | S3 / bit2 | Multi-reference bit 2 | DI5 |
| Blue | COM | Digital common | COM/DCM |
Wire colours vary by batch — confirm by terminal name. Set CV100 NPN/PNP jumper to match NK105 (NPN/sinking typical).
Coolant interlock (strongly recommended): wire a flow switch into a CV100 free digital input set as "external fault" so the spindle cannot run without coolant flow. Power: Mains R/S/T (380 V) via breaker+filter → CV100; U/V/W → spindle (phase order = direction); heavy earth from spindle, VFD and frame to one point.
4. Kinco CV100 Parameters
Basic (P0):
| Param | Set | Description |
|---|---|---|
| P0.01 | 1 | Command source = terminal |
| P0.02 | 6 | Frequency source = multi-reference |
| P0.04 | 400.00 | Max frequency (300 if 18,000 RPM) |
| P0.05 | 400.00 | Upper limit |
| P0.06 | 0.00 | Lower limit |
| P0.08 | 12.0 | Accel time (s) |
| P0.09 | 12.0 | Decel time (s) |
Motor (P1) — from nameplate. Wrong voltage destroys the spindle:
| Param | Set | Notes |
|---|---|---|
| P1.01 | Nameplate kW | e.g. 5.5 |
| P1.02 | Nameplate V | 380 V (verify) |
| P1.03 | Nameplate A | Rated current |
| P1.04 | 400.00 | Rated frequency |
| P1.05 | 24000 | Rated RPM (2-pole) |
Inputs (P5):
| Param | Set | Function |
|---|---|---|
| P5.00 (DI1) | 1 | Forward run |
| P5.02 (DI3) | 12 | Multi-reference terminal 1 |
| P5.03 (DI4) | 13 | Multi-reference terminal 2 |
| P5.04 (DI5) | 14 | Multi-reference terminal 3 |
| P5.0x spare | 10 | (Optional) External fault — coolant switch |
Multi-reference speeds (PC) — % of P0.04, must match NK105 handle:
| Gear | Param | % | Hz | RPM |
|---|---|---|---|---|
| S1 | PC.00 | 0 | 0 | 0 (Stop) |
| S2 | PC.01 | 25 | 100 | 6,000 |
| S3 | PC.02 | 37.5 | 150 | 9,000 |
| S4 | PC.03 | 50 | 200 | 12,000 |
| S5 | PC.04 | 62.5 | 250 | 15,000 |
| S6 | PC.05 | 75 | 300 | 18,000 |
| S7 | PC.06 | 87.5 | 350 | 21,000 |
| S8 | PC.07 | 100 | 400 | 24,000 |
5. NK105 Controller Setup
Menu → Parameter → Spindle (manufacturer password may be needed).
Spindle type: Multi-step / gear (binary), not analog 0–10 V Number of gears: 8 Start/stop delay: 5000 ms each Gear table S1–S8: 0 / 6,000 / 9,000 / 12,000 / 15,000 / 18,000 / 21,000 / 24,000 RPM (match Section 4)
6. Commissioning Sequence
1. Coolant first — fill, run pump, confirm flow and no leaks
2. Pre-power: wiring matches Section 3; pull-test; U/V/W + earth tight; breaker off
3. Power-up: CV100 shows 0.00; NK105 boots
4. Enter parameters (4.1–4.4), save, power-cycle, verify
5. NK105 setup (Section 5)
6. Functional test: coolant ON → spindle ON at S2 → 6,000 RPM; step gears up; OFF ramps down. Wrong direction → power off, swap two of U/V/W
7. Sign-off: run S8 5 min, coolant warm not hot, body <50 °C, test-cut, log values
7. Troubleshooting
| Symptom | Likely cause | Action |
|---|---|---|
| Won't start | FWD not reaching DI1, or coolant interlock open | Check P5.00=1; confirm flow switch; meter DI1 to COM |
| Only 4 speeds | A multi-ref bit dead (usually bit0/DI3) | Cycle gears, meter DI3/DI4/DI5; check P5.02–04 |
| Wrong RPM | PC values ≠ NK105 labels | Re-enter Section 4 to match Section 5 |
| Overvoltage on stop | Decel too fast | Raise P0.09 to 15 s; brake resistor |
| Overload/overheat | Wrong P1.03, or no coolant | Verify rated current; confirm pump & flow |
| Hot spindle, cold coolant | Flow blocked/reversed | STOP; check pump direction, kinks, filter |
8. Quick Reference
P0.01=1 · P0.02=6 · P0.04=400 · P0.08=12 · P0.09=12 P1.01..05 = nameplate (kW/V/A/Hz/RPM) P5.00=1 · P5.02=12 · P5.03=13 · P5.04=14 PC.00=0 · PC.01=25 · PC.02=37.5 · PC.03=50 · PC.04=62.5 · PC.05=75 · PC.06=87.5 · PC.07=100
Golden rule for water-cooled: coolant flows BEFORE the spindle spins, every time. Fit a flow interlock and this spindle will outlast the machine.