NK105 + Folinn H110T
Air-cooled spindle


1. Overview
The Folinn H110T (also sold as Hold/Folinn H110 series) is a common VFD for air-cooled HQD spindles up to ~6 kW. With a Weihong NK105 controller the spindle runs in multi-step terminal mode, the operator selecting gears S1–S8 from the handle. Air-cooled spindles need clean airflow and a minimum running speed; they tolerate dust poorly, so keep the fan path clear.
2. Required Hardware
| Item | Specification |
|---|---|
| VFD | Folinn H110T, sized to spindle (e.g. H110T 5R5G/7R5P for 5.5 kW) |
| Controller | Weihong NK105 (G2/G3) + terminal board |
| Spindle | HQD air-cooled, 2-pole, 400 Hz (verify nameplate V/A) |
| Control cable | Shielded multi-core 0.5–1.0 mm² |
| Power cable | 4-core shielded (U/V/W + earth), sized to power |
3. Wiring — Control (NK105 board → H110T inputs)
| Wire (typical colour) | NK105 output | Function | H110T terminal |
|---|---|---|---|
| Red | SPIN-FWD | Run forward ON/OFF | S1 (FWD) |
| Green | bit0 | Multi-step bit 0 | S3 |
| Black | bit1 | Multi-step bit 1 | S4 |
| Yellow | bit2 | Multi-step bit 2 | S5 |
| Blue | COM | Digital common | COM |
Wire colours vary by batch — confirm by terminal name. Set the H110T NPN/PNP selection to match the NK105 output (NPN/sinking typical).
Power: Mains R/S/T via breaker+filter → H110T input; U/V/W → spindle (phase order = direction); solid earth from spindle, VFD, frame to one point.
4. Folinn H110T Parameters
Basic (F0):
| Param | Set | Description |
|---|---|---|
| F0.02 | 1 | Command source = terminal |
| F0.03 | 6 | Frequency source = multi-step |
| F0.04 | 400.00 | Max frequency (300 if 18,000 RPM) |
| F0.05 | 400.00 | Upper limit |
| F0.06 | 0.00 | Lower limit |
| F0.07 | 8.0 | Accel time (s) |
| F0.08 | 8.0 | Decel time (s) |
Motor (F1) — from nameplate. Wrong voltage burns the spindle:
| Param | Set | Notes |
|---|---|---|
| F1.01 | Nameplate kW | e.g. 5.5 |
| F1.02 | Nameplate V | 220 or 380 V |
| F1.03 | Nameplate A | Rated current |
| F1.04 | 400.00 | Rated frequency |
| F1.05 | 24000 | Rated RPM (2-pole) |
Inputs (F5):
| Param | Set | Function |
|---|---|---|
| F5.01 (S1) | 1 | Forward run |
| F5.03 (S3) | 16 | Multi-step terminal 1 |
| F5.04 (S4) | 17 | Multi-step terminal 2 |
| F5.05 (S5) | 18 | Multi-step terminal 3 |
Note: Folinn multi-step function codes are commonly 16/17/18 — confirm against your unit's manual, as the trap on this VFD (like the DV203) is multi-step terminals defaulting to other functions.
Multi-step speeds (F-step group) — % of F0.04, match NK105 handle:
| Gear | Param | % | Hz | RPM |
|---|---|---|---|---|
| S1 | step0 | 0 | 0 | 0 (Stop) |
| S2 | step1 | 25 | 100 | 6,000 |
| S3 | step2 | 37.5 | 150 | 9,000 |
| S4 | step3 | 50 | 200 | 12,000 |
| S5 | step4 | 62.5 | 250 | 15,000 |
| S6 | step5 | 75 | 300 | 18,000 |
| S7 | step6 | 87.5 | 350 | 21,000 |
| S8 | step7 | 100 | 400 | 24,000 |
5. NK105 Controller Setup
Menu → Parameter → Spindle.
Spindle type: Multi-step / gear (binary), not analog Number of gears: 8 Start/stop delay: 5000 ms each Gear table S1–S8: 0 / 6,000 / 9,000 / 12,000 / 15,000 / 18,000 / 21,000 / 24,000 RPM (match Section 4)
6. Commissioning Sequence
1. Pre-power: wiring per Section 3; pull-test; U/V/W + earth tight; fan path clear; breaker off
2. Power-up: H110T shows 0.00; NK105 boots
3. Enter parameters, save, power-cycle, verify
4. NK105 setup (Section 5)
5. Test: spindle ON at S2 → 6,000 RPM; step gears up; OFF ramps down. Wrong direction → power off, swap two of U/V/W
6. Sign-off: run S8 5 min (body warm not hot), no vibration, test-cut, log values
7. Troubleshooting
| Symptom | Likely cause | Action |
|---|---|---|
| Won't start | FWD not reaching S1 | Check F5.01=1; meter S1 to COM |
| Runs alternate/paired gears | Multi-step terminal default wrong | Set F5.03/04/05 to multi-step (16/17/18) |
| Wrong RPM | Step values ≠ NK105 labels | Re-enter Section 4 to match Section 5 |
| Overvoltage on stop | Decel too fast | Raise F0.08 to 12 s; brake resistor |
| Overload/overheat | Wrong F1.03, dust-blocked fan | Verify rated current; clean fan/intake |
| Spindle hot | Air path blocked, running too slow | Clear airflow; avoid sustained low RPM |
8. Quick Reference
F0.02=1 · F0.03=6 · F0.04=400 · F0.07=8 · F0.08=8 F1.01..05 = nameplate (kW/V/A/Hz/RPM) F5.01=1 · F5.03=16 · F5.04=17 · F5.05=18 steps: 0 / 25 / 37.5 / 50 / 62.5 / 75 / 87.5 / 100 %
Air-cooled rule: keep the fan path clean and don't run sustained below ~6,000 RPM — air-cooled spindles rely on speed and airflow to stay cool. Need help? WhatsApp AZ Inspired: +91 98764 32933 · For qualified technicians. Folinn function codes vary by firmware — verify multi-step codes against your unit's manual. Verify all values against your spindle nameplate.